| Ultra Filtration Drinking Water Treatment of mains tap water | ||||||
| Prevents bacteria including Legionella, Viri , Fungi and parasites such as cryptosporidium entering your water supply click here for prices & operating manual | ||||||
|
water flow m3/h |
||||||
| Single column systems | code | filter element |
|
|
|
|
![]() |
4.6.4.1 | 4.6.4.30 | 0,3 m3/h | 0.08 m3/h | 0.04 m3/h | 0.03 m3/h |
| 4.6.4.2 | 4.6.4.31 | 0,55 | 0.14 | 0.08 | 0.04 | |
| 4.6.4.3 | 4.6.4.32 | 0,8 | 0.21 | 0.11 | 0.06 | |
| 4.6.4.4 | 4.6.4.33 | 1,1 | 0.3 | 0.15 | 0.08 | |
| 4.6.4.5 | 4.6.4.34 | 2.3 | 0.6 | 0.32 | 0.16 | |
| Multi column systems | ||||||
![]() |
4.6.4.7 | 3 x 4.6.4.33 | 3.3 | 0.9 | 0.5 | 0.3 |
| 4.6.4.8 | 2 x 4.6.4.34 | 4.4 | 1 | 0.6 | 0.5 | |
| 4.6.4.9 | 3 x 4.6.4.34 | 7 | 2 | 1 | 0.7 | |
| 4.6.4.10 | 4 x 4.6.4.34 | 9 | 2.5 | 1.3 | 0.9 | |
| 4.6.4.11 | 5 x 4.6.4.34 | 11 | 3 | 1.6 | 1.1 | |
| 4.6.4.12 | 6 x 4.6.4.34 | 14 | 4 | 2 | 1.4 | |
| 4.6.4.13 | 7 x 4.6.4.34 | 16 | 4.5 | 2.5 | 1.6 | |
| 4.6.4.14 | 8 x 4.6.4.34 | 18 | 5 | 3 | 1.8 | |
| 4.6.4.15 | 9 x 4.6.4.34 | 20 | 5.5 | 3.3 | 2 | |
| 4.6.4.16 | 10 x 4.6.4.34 | 23 | 6 | 3.6 | 2.3 | |
| 4.6.4.17 | 11 x 4.6.4.34 | 25 | 7 | 4 | 2.5 | |
| 4.6.4.18 | 12 x 4.6.4.34 | 27 | 7.5 | 4.3 | 2.7 | |
| Dentists system | ||||||
![]() |
3 litres per minutes, supplied complete in a case | |||||
| Replacement filter elements | code | |||||
| replacement ultra filter elements. The replacement frequency depends upon water quality. Typical frequency is 5 years. Product water quality should be occasionally checked for bacteria. Our dip slides may be used | 4.6.4.30 | 50mm x 510mm filter elements | ||||
| 4.6.4.31 | 63mm x 510mm filter elements | |||||
| 4.6.4.32 | 75mm x 510mm filter elements | |||||
| 4.6.4.33 | 90mm x 510mm filter elements | |||||
| 4.6.4.34 | 90mm x 1000mm filter elements | |||||
| Fittings | code | |||||
| 4.6.4.35 | non return valve, 1/2" only for 4.6.4.1 | |||||
| 4.6.4.36 | valve on water inlet, 1/2" only for 4.6.4.1 | |||||
| 4.6.4.37 | solenoid valve for flushing, 1/2" used on all units | |||||
| 4.6.4.38 | timer for automatic flushing, 230v ac used on all units | |||||
| 4.6.4.39 | non return valve, 3/4" only for 4.6.4.2 to 4.6.4.5 | |||||
| valve on water inlet, 3/4" only for 4.6.4.2 to 4.6.4.5 | ||||||
| Technical specification | click here for prices |
| Type of filtration : | Ultra filtration |
| Pore size of membrane : | 0.01 µm |
| Type of membrane : | Multibore / SevenBore |
| Number of bores per fiber : | 7 |
| Material of membrane : | Polyethersulfone |
| Diameter bores ID : | 0.9 mm |
| Diameter fiber OD : | 4.2 mm |
| MWCO : | 100 – 150 kD |
| Maximum system pressure : | 10 bar |
|
Trans membrane pressure : |
operation: 0.5 – 1 bar |
| maximum: | 2.5 bar |
| Productivity clean water at 25°C : | < 1000 l/m²/bar/h |
| pH range during operation : | 3 – 10 |
| Maximum water temperature : | 40°C |
| Soaking time during cleaning : | 5 min |
| pH range during cleaning : | 1 – 13 |
| Disinfection chemicals : | 50
– 100 ppm hypochlorite (NaOCl) : 100 – 200 ppm hydrogen peroxide (H²O²) |